Features
Automatic overload protection
Convenient lighted on/off switches
Available in 70, 150 and 250VA outputs
Offered in standard 120 volt, 60 Hz models
Two duplex receptacles allow several pieces of equipment to economically share the same source of regulated power
Specifications
Input:
Voltage: 120 V
Input Voltage Range: +10% to -20% of input nominal voltage
Control:
Lighted Enable Switch
Output:
Voltage: 120 V
Voltage Regulation: ±3% for an input line variation of +10% to -20%. Output will remain within NEMA voltage specifications for input voltages as low as 65% of nominal. No loss of output for line loss of three milliseconds.
Harmonic Distortion: Less than 3% total RMS content at full load
Noise Reduction:
Common mode noise rejection exceeds 120 dB (DC to 1 MHz)
Transverse mode noise rejection exceeds 60 dB (10 KHz to 1 MHz)
Protection:
Input: Surge suppression module
Output: Surge suppression module and ferroresonant technology suppresses ANSI/IEEE C62.41-1980 Class A and B waveforms to safe levels (formerly IEEE 587-1980)
Efficiency:
90% at full load (typical)
Reliability:
25-year continuous life, average
Operating Temperature:
-4 °F to 122 °F (-20 °C to 50 °C)
Construction:
Cruciform-type construction with precision die-cut shunts, gaps and spacing between windings
Approvals:
UL listed to UL1012
CSA certified to CSA C22.2-66
Dimensions:
(L × W × H)
9.25 × 6.75 × 6.25 in
Warranty:
One-year limited